PPD Project Planning & Design
Environmental conditions, building design, structural systems, building envelope, and systems integration.
PPD Field Guide
Every topic covered for Project Planning & Design, written for the exam rather than the textbook. Tap any heading to open it.
01 Energy & Envelope Standards
Key standards
| Standard | Topic |
|---|---|
| IECC | International Energy Conservation Code |
| ASHRAE 90.1 | Energy Standard for Buildings Except Low-Rise Residential |
| ASHRAE 62.1 | Ventilation for Acceptable IAQ |
| ASHRAE 55 | Thermal Comfort |
Climate zones (IECC)
| Zone | Climate | Typical |
|---|---|---|
| 1 | Very Hot | Miami, Honolulu |
| 2 | Hot | Houston, Phoenix |
| 3 | Warm | LA, Atlanta |
| 4 | Mixed | DC, NYC, St. Louis |
| 5 | Cool | Chicago, Boston |
| 6 | Cold | Minneapolis |
| 7 | Very Cold | Duluth, Anchorage |
| 8 | Subarctic | Northern Alaska |
Sub-classifications: A (moist), B (dry), C (marine)
Envelope U-factor prescriptive (commercial Zone 5)
| Component | U-factor |
|---|---|
| Walls (steel framed) | 0.064 |
| Walls (mass) | 0.080 |
| Roof above deck | 0.039 (R-30 ci) |
| Floor over outside air | 0.038 |
| Glazing | 0.36-0.42 |
| Slab edge | F-0.54 |
Glazing performance
| Metric | Description |
|---|---|
| U-factor | Heat transmission (lower better) |
| SHGC | Solar Heat Gain Coefficient (0-1) |
| VT | Visible Transmittance (0-1) |
| LSG | Light-to-Solar-Gain (VT ÷ SHGC) |
SHGC targets:
- Cold climate: 0.40-0.55 (capture winter solar)
- Hot climate: 0.25 or lower (block sun)
- Mixed: 0.25-0.40
Vapor retarder placement
| Climate | Placement |
|---|---|
| Cold (Zone 5+) | Interior (warm side) |
| Hot/Humid (Zone 1-3A) | Exterior (warm humid side) |
| Mixed (Zone 4) | Vapor-open assembly or smart retarder |
Air barrier
Required by IECC and ASHRAE 90.1. Continuous around envelope. Testing:
- Blower door (residential)
- Whole-building pressurization (commercial)
Air leakage often bigger moisture issue than vapor diffusion.
Continuous Insulation (ci)
Required by IECC in many zones. Outboard of studs eliminates thermal bridging (which reduces effective R-value 30-50%).
02 Structural Rules of Thumb
Beam depth estimates
| System | Span/Depth Ratio |
|---|---|
| Steel W-beam | L/20 (L/15-L/24 range) |
| Steel joist (K-series) | L/20 |
| Steel joist (LH long-span) | L/20 |
| Wood joist | L/15-L/20 |
| Glulam beam | L/16-L/20 |
| Concrete one-way slab | L/24 (SS), L/28 (cont) |
| Concrete two-way slab | L/30 |
| Post-tensioned slab | L/40+ |
| Concrete beam | L/12-L/16 |
Column sizing
Tributary area × load = axial demand
Office typical: ~70 psf total (DL + LL)
- W-shape: select from tables based on axial + slenderness
- HSS: efficient compression, cleaner appearance
- Concrete: reinforced or post-tensioned
Foundation systems
| System | When |
|---|---|
| Spread footing | Soil bearing adequate (≥2,000 psf), no expansion, no high water table |
| Strip footing | Continuous load (load-bearing walls) |
| Mat foundation | Weak/uniform soils, high water table |
| Drilled shaft / pier | Transfer load to deeper layer |
| Driven pile | Deep competent layer, urban (timber/steel H/concrete) |
| Helical screw | Light loads, retrofit, low vibration |
Frost line depth (foundations below)
| Region | Depth |
|---|---|
| S Florida | 0" |
| Mid-Atlantic | 24-30" |
| Midwest | 36-42" |
| N New England | 48-54" |
| N Minnesota | 60" |
Soil bearing capacity (allowable)
| Soil | Bearing |
|---|---|
| Bedrock | 8,000-25,000+ psf |
| Dense sand | 3,000-5,000 psf |
| Stiff clay | 2,000-4,000 psf |
| Loose sand | 1,500-3,000 psf |
| Soft clay | <1,500 psf (deep foundations) |
Loads (typical)
| Load Type | psf |
|---|---|
| Office LL | 50 |
| Office partitions | 15 |
| Retail LL | 75-100 |
| Residential LL | 40 |
| Assembly fixed | 60 |
| Assembly movable | 100 |
| Library reading | 60 |
| Library stacks | 150 |
| Parking | 40 (passenger), 80 (trucks) |
| Roof | 20 (snow varies by location) |
Lateral systems
| System | R | Performance |
|---|---|---|
| Special steel moment | 8 | High ductility |
| Special steel braced | 6 | High strength |
| Special concrete moment | 8 | High ductility |
| Special shear wall | 6 | High strength |
| Ordinary moment | 3 | Limited ductility |
Higher R = lower seismic force = more deformation expected.
Seismic base shear
V ≈ Cs × W
- W = building weight
- Cs depends on site class, spectral acceleration, period, R, Ie
- Heavier buildings get more seismic force
03 HVAC Systems — Selection by Building Type
System types
| System | Application | Pros | Cons |
|---|---|---|---|
| VAV (Variable Air Volume) | Office, larger commercial | Energy efficient, zoning | Complex controls |
| CAV (Constant Air Volume) | Smaller buildings, critical spaces | Simpler | Less efficient |
| VRF/VRV | Mid-size commercial, residential | Heat recovery between zones | Higher upfront |
| Chilled Beam | Office, lab | Efficient, quiet, low ductwork | Humidity control critical |
| Radiant (floor/ceiling) | Residential, civic | Comfort, low air movement | Slower response |
| Packaged RTU | Big box, warehouse, low-rise | Simple, low cost | Less control |
| Geothermal HP | Mid-size with balanced loads | Very efficient, long life | High upfront, drilling |
Cooling tonnage rules of thumb
| Building | SF/ton |
|---|---|
| Restaurant | 100-200 |
| Healthcare | 250-300 |
| Retail | 300-400 |
| Office (efficient) | 400-500 |
| School | 300-500 |
| Library | 400-600 |
| Warehouse | 1,000+ |
Air change rates (ASHRAE 62.1)
| Space | OA rate |
|---|---|
| Office | 5 cfm/person + 0.06 cfm/SF |
| Conference | 5 cfm/person + 0.06 cfm/SF |
| Classroom | 10 cfm/person + 0.12 cfm/SF |
| Patient room | 25 cfm/person |
| Operating room | 20+ ACH |
| Lab | 6-10+ ACH (negative pressure) |
| Restroom | 50 cfm/WC or 25 cfm/SF exhaust |
Energy recovery (ERV/HRV)
- ERV: sensible + latent (humidity) transfer
- HRV: sensible only
- 50-75% effectiveness typical
- Required by ASHRAE 90.1 above certain airflow thresholds
Economizer
- Free cooling using outside air when conditions favorable
- ASHRAE 90.1 requires above certain capacity
- Climate-dependent value (huge in temperate zones)
DCV (Demand-Controlled Ventilation)
CO2-based airflow modulation. Energy savings in spaces with variable occupancy (conference rooms, classrooms, assembly).
04 Electrical System Sizing & Distribution
Service sizing (residential)
| Type | Service |
|---|---|
| Small residence | 100 A |
| Typical new home | 200 A |
| Large + EV + HVAC | 200-400 A |
Commercial service
Sized per NEC Article 220 load calc:
- Lighting (per LPD × area + factors)
- Receptacles (180 VA per outlet, but factors apply)
- HVAC (largest motor + 100% other motors)
- Specific loads (kitchens, elevators, etc.)
- Demand factors per use type
Voltage systems
| System | Use |
|---|---|
| 120/240 V single phase | Residential, small commercial |
| 120/208 V 3-phase | Light commercial |
| 277/480 V 3-phase | Commercial (lighting, motors) |
| 480/277 V | Large commercial industrial |
| 2400/4160 V | Industrial, large institutional |
Branch circuit standards
- 15 A: lighting, general outlets
- 20 A: kitchens, bathrooms (GFCI required), commercial general
- 30 A: dryers, water heaters
- 50 A: ranges, EV chargers
Panel locations
- Accessible (NEC 240.24)
- 30" wide × 36" deep clearance (working space)
- Not in bathrooms, closets with combustibles
- Headroom 6'-6" minimum
Conduit & wire
- EMT (electrical metallic tubing): light commercial, exposed
- RMC/IMC (rigid): hazardous, industrial, exterior
- PVC: underground, wet locations
- AC/MC cable (armored): commercial, accessible
Grounding & bonding
Critical for safety. NEC Article 250:
- Service ground rod or building grounding electrode system
- Equipment grounding conductor through all branch circuits
- Bonding jumpers at metallic systems
Emergency power
| Type | Use |
|---|---|
| Emergency (NEC 700) | Life safety: egress, exit signs, alarms — 10-sec transfer |
| Legally required standby (NEC 701) | Heating/refrigeration, communications — 60-sec |
| Optional standby (NEC 702) | Convenience — variable |
05 Plumbing System Fundamentals
Water supply sizing
- Water Supply Fixture Units (WSFU) per IPC table
- Pressure: 40-80 psi typical from utility (50-60 ideal)
- Friction loss + elevation + fixture demand
- Main 3/4"-1" residential typical; commercial sized per WSFU
Drainage Fixture Units (DFU)
| Fixture | DFU |
|---|---|
| WC (flush valve) | 6-8 |
| WC (tank) | 3-4 |
| Lavatory | 1 |
| Shower | 2 |
| Tub | 2 |
| Kitchen sink | 2 |
| Floor drain | 2 |
| Dishwasher | 2 |
Pipe sizing — drainage
| Pipe size | Max DFU (horizontal branch) |
|---|---|
| 1-1/2" | 3 |
| 2" | 6 |
| 3" | 20 |
| 4" | 160 |
| 6" | 620 |
Venting
- Every fixture trap requires vent
- Vent termination 6" above flood level rim of fixtures (general)
- Vent extension 12" above roof in cold climate (frost closure)
- Combined drain/vent allowed for some fixtures (wet venting)
Hot water
- Storage tank vs tankless vs heat pump
- Recirculation for distant fixtures (energy code may require if length exceeds threshold)
- 120°F at fixtures (scald prevention); 140°F at tank (Legionella prevention)
- Mixing valves for showers/lavatories
Fixture counts (IBC/IPC)
Group B (office, sprinklered):
- Lavatories: 1 per 40 occupants
- WCs: 1 per 25 for first 50, then 1 per 50
- Drinking fountains: 1 per 100 occupants (or bottle filler)
Group A-2 (restaurant):
- Higher density requirements
- Per occupant load × 1/75 (M+F separate)
Code references
- IPC (International Plumbing Code) — most jurisdictions
- UPC (Uniform Plumbing Code) — Western states
- NFPA 99 healthcare-specific
- ANSI/ASHRAE 188 (Legionellosis prevention)
06 Roofing Systems Comparison
Low-slope (commercial) systems
| System | Description | Life | Notes |
|---|---|---|---|
| TPO | Thermoplastic Polyolefin | 20-30 yr | White, reflective, common |
| PVC | Polyvinyl Chloride | 20-30 yr | More chemical-resistant |
| EPDM | Synthetic rubber | 30+ yr | Black or white, durable |
| Modified Bitumen | Asphalt + polymer | 15-25 yr | Torch or self-adhered |
| BUR (Built-up) | Multiple ply + asphalt | 20-30 yr | Heavy, well-proven |
| Liquid-applied | Fluid membrane | 15-25 yr | Complex shapes |
| Metal (standing seam) | Metal panels | 40-50 yr | Higher initial, long life |
Slopes
- Low-slope: ≤2:12 (typically 1/4" per foot minimum drainage)
- Steep-slope: >2:12 (shingles, tiles, metal)
Drainage requirements
- Primary: handles design storm (often 100-year)
- Overflow: backup; scuppers or secondary drains 2"+ above primary
- Critical: ponding water can collapse roof
Insulation placement
- Above deck (most common low-slope): no thermal bridging, cool roof
- Below deck (attic): cheaper but thermal bridging through joists
- Mass timber/exposed structure: insulation above deck
Cool roof (LEED, energy codes)
- SRI ≥29 (low-sloped) or ≥39 (steep) per LEED v4.1
- White TPO/PVC easily exceeds (SRI 80+)
- Reduces heat island, building cooling load
Green roof
- Extensive: 3-6" media, lightweight (10-35 psf wet), sedums
- Intensive: 8"+ media, heavy (80-150+ psf wet), rooftop gardens
- Stormwater retention, biodiversity, insulation, longer membrane life
Photovoltaic
- BIPV (Building Integrated PV): replaces membrane
- Rack-mounted: above existing roof
- Adds load (5-8 psf typical)
- Structural review required
Flashing detailing
- Step flashing at vertical surfaces
- Counterflashing over base flashing
- Pipe boots (pre-fabricated)
- Drains: 2-piece with clamping ring
- Coordination with parapet, walls, equipment
07 Daylighting & Glazing Design
Daylight Factor (DF)
Ratio of interior to exterior illuminance under overcast sky:
- 2% adequate for general office task
- 5%+ preferred
- Toplighting (skylights, monitors) gives more uniform DF
- Sidelighting usable to ~2× ceiling height from window
Glazing performance metrics
| Metric | Description | Target |
|---|---|---|
| U-factor | Heat transmission | Lower = better insulator |
| SHGC | Solar Heat Gain Coefficient (0-1) | Climate-dependent |
| VT | Visible Transmittance (0-1) | Higher = more daylight |
| LSG | Light-to-Solar Gain (VT ÷ SHGC) | Higher = more daylight per heat |
SHGC targets by climate
| Climate | SHGC |
|---|---|
| Cold (Zone 5+) | 0.40-0.55 (capture winter solar) |
| Mixed (Zone 4) | 0.25-0.40 |
| Hot (Zone 1-3) | 0.25 or lower |
Low-e coatings
- Hard coat (pyrolytic): durable, can face outside
- Soft coat (sputtered): better performance, must be in insulating air space
- Spectrally selective: high VT, low SHGC
Shading strategies
- Overhangs (south): depth ≈ 50% of glazing height (temperate)
- Vertical fins (east/west): low-angle sun harder to control
- Exterior shades (blinds, screens): most effective at blocking solar before glass
- Interior shades: less effective (heat already inside) but glare control
Light shelves
- Horizontal element on interior of south windows
- Bounces light deeper into space (off ceiling)
- Reduces glare near window, increases daylight at back
- Combined with proper ceiling reflectance (>70%)
Daylight harvesting controls
- Photosensors dim electric lights based on daylight available
- Required by ASHRAE 90.1 in daylit zones
- 25-50% lighting energy savings
Glare control
- Discomfort glare: subjective, distracting
- Disability glare: prevents seeing task
- Mitigation: blinds, fritted/screened glass, exterior shading, indirect lighting
Hurricane glazing (HVHZ zones)
- ASTM E1996 + E1886 test standards
- Laminated glass + anchored frame as system
- Required: Miami-Dade, Broward, coastal FL
- Alternative: shutters per code
08 Acoustic Design
Sound metrics
| Metric | Description |
|---|---|
| STC | Sound Transmission Class (airborne — walls, floors, doors) |
| IIC | Impact Insulation Class (impact — floor/ceiling) |
| NRC | Noise Reduction Coefficient (absorption — 0-1) |
| NIC | Noise Isolation Class (field-measured) |
| dBA | Decibels A-weighted (sound level) |
STC ratings (typical)
| Assembly | STC |
|---|---|
| Hollow core door | 20-25 |
| Single layer GWB stud wall | 33-35 |
| Double layer GWB stud wall | 45-50 |
| Office demising wall | 45-50 |
| Apartment unit walls (code) | 50+ |
| Hotel between rooms | 50-55 |
| Theater walls | 60+ |
| Recording studio | 70+ |
IIC ratings (floor-ceiling)
| Assembly | IIC |
|---|---|
| Slab only | 25-30 |
| Carpet + pad on slab | 50-60 |
| Tile/wood on slab | 30-40 |
| Code apartments | 50+ |
Detail matters
- Penetrations: outlets back-to-back, plumbing, ducts destroy STC
- Doors: STC of weakest element governs (door usually ≪ wall)
- Ceiling continuation: walls to deck (not just to ceiling) for true STC
- Flanking: sound around or through adjacent assemblies
Absorption (interior acoustics)
- NRC 0.0-1.0 (1.0 = total absorption)
- Acoustic ceiling tiles: NRC 0.65-0.95
- Carpet: NRC 0.20-0.55
- Hard surfaces: NRC 0.00-0.05
Reverberation Time (RT)
Time for sound to decay 60 dB:
- Speech intelligibility: 0.5-1.0 sec
- Music concert hall: 1.5-2.0 sec
- Cathedral: 4-6+ sec
- Calculated: RT60 = 0.049 × V ÷ (Σ Sα) [V volume, S surface area, α absorption]
Background noise (NC/RC)
- Private office: NC 30-35
- Open office: NC 35-40
- Library reading: NC 30-35
- Hospital exam: NC 30-35
- Classroom: NC 30 (ANSI standard)
- Auditorium: NC 20-25
ANSI standard S12.60 (classrooms)
- Background noise ≤35 dBA
- RT ≤0.6 sec (small) or 0.7 sec (large)
- Critical for speech intelligibility, especially for hearing-impaired
09 Fire Protection Systems
Sprinkler standards
| Standard | Application |
|---|---|
| NFPA 13 | Full system; unlocks IBC trade-offs |
| NFPA 13R | Residential up to 4 stories |
| NFPA 13D | 1-2 family dwellings (life safety only) |
NFPA 13 IBC trade-offs unlocked
- Area increases (200% under §506.3)
- Height increases (+20 ft + 1 story per §504)
- Travel distance increased (e.g., B 200 → 300 ft)
- Reduced fire ratings (e.g., 1-hr corridors → 0-hr in many cases)
- Dead-end corridors increased (B 20 → 50 ft)
Sprinkler hazard classifications
| Class | Density (gpm/sf) | Examples |
|---|---|---|
| Light Hazard | 0.10 | Office, school, hospital, hotel |
| Ordinary 1 | 0.15 | Restaurant, retail |
| Ordinary 2 | 0.20 | Print shop, warehouse |
| Extra Hazard | 0.30-0.60 | Aerosol storage, plastics |
Sprinkler systems
- Wet pipe (most common): water in pipes ready to flow
- Dry pipe (freeze risk): air in pipes, water at valve
- Pre-action (sensitive areas): requires two events to activate
- Deluge (high hazard): all heads open, manual trigger
Standpipes (NFPA 14)
| Class | Hose | Use |
|---|---|---|
| Class I | 2-1/2" | Fire department only |
| Class II | 1-1/2" | Trained occupants |
| Class III | Both | Both populations |
Required for buildings above 30 ft above lowest fire dept access (varies).
Fire alarm (NFPA 72)
- Initiating devices: manual pull, smoke detector, heat detector, water flow
- Notification appliances: horn/strobe, voice evacuation, visual for hearing-impaired
- Control panel: monitors, supervises, signals
- Power: AC + 24-hr battery backup
- Voice evacuation required: Group A 1000+ occupants, high-rises, certain occupancies
Fire-rated assemblies
- Walls: per UL design (e.g., UL U419 for 1-hr GWB)
- Doors: per NFPA 80 (e.g., 90-min in 2-hr wall)
- Penetrations: firestopping per ASTM E814/UL 1479
- Glazing: fire-protective vs fire-resistive (different criteria)
Smoke control
- Smoke barriers: contain smoke (I-2 every 22,500 SF max)
- Smoke partitions: less stringent than barriers
- Pressurization: stair pressurization in high-rise
- Smoke exhaust: atria, malls
10 Vertical Transportation
Elevator types
| Type | Application | Speed | Travel |
|---|---|---|---|
| Hydraulic | Low-rise (≤5 stories) | ≤150 fpm | ≤60 ft |
| MRL (Machine-Room-Less) | Mid-rise | 150-500 fpm | ≤200 ft |
| Traction (geared) | Mid-rise | 100-500 fpm | Up to 250 ft |
| Traction (gearless) | High-rise | 500-1,800 fpm | Unlimited |
| Destination dispatch | Tall buildings | Variable | Optimized |
Capacity & sizing
| Use | Capacity | Notes |
|---|---|---|
| Office | 2,500-4,000 lb | 16-25 person |
| Residential | 2,500-3,500 lb | 16-21 person |
| Service | 4,500-5,000 lb | Carts, larger pieces |
| Hospital | 5,000-6,000 lb | Stretcher/gurney |
| Freight | Per loading | Heavy equipment |
Elevator banking (population analysis)
Handling Capacity (HC) = passengers carried in 5 min ÷ population × 100
- Office target: 12-15%
- Hospital target: 8-10%
- Residential target: 5-8%
Average Interval (AI) = waiting time between cars
- Office: 25-35 seconds acceptable
- Premium: <25 seconds
Shaft & machine room
- MRL: no machine room, hoist machine in shaft
- Traditional: machine room above (overhead) or below (basement)
- Shaft sized per car capacity + clearances
- Pit depth per code (5-10+ ft, varies)
- Overhead clearance above top floor
Code compliance
- ASME A17.1: Safety Code for Elevators and Escalators
- ADA: accessible: 80" car min, controls 15-48" reach, audible signals
- Fire service operation: Phase I (recall), Phase II (firefighter operation)
- Emergency power: required for high-rise (one car at a time)
Escalators
- 24-30" tread width (typical commercial)
- 30° incline (typical)
- 100-120 fpm typical
- Sized for peak flow
- Two-direction common; one-direction in lower-volume
Lifts & dumbwaiters
- Wheelchair lifts: ADA accessible vertical transport (short distances)
- Platform lifts: industrial/freight
- Dumbwaiters: materials only, not occupied
- Some loophole avoidance in code (compliance check required)
11 Foundations — Systems & Selection
Shallow foundations
| Type | When |
|---|---|
| Spread footing | Concentrated load, adequate bearing |
| Strip footing | Continuous load (bearing wall) |
| Combined footing | Adjacent columns close to property line |
| Mat (raft) | Weak/uniform soils, high water table |
Deep foundations
| Type | When |
|---|---|
| Driven pile (timber) | Light loads, accessible |
| Driven pile (steel H) | Heavy loads, urban (noise/vibration issues) |
| Driven pile (precast concrete) | Medium-heavy loads |
| Drilled shaft / caisson | Heavy loads, less vibration |
| CFA (Continuous Flight Auger) | Loose to medium soils |
| Helical screw | Light loads, retrofit, low vibration |
| Micropile | Restricted access, retrofit, restoration |
Pile capacity
- End bearing: load transferred to dense layer or rock
- Friction: load transferred through skin friction along shaft
- Combination: most piles in practice
Soil bearing capacity (allowable)
| Soil | psf |
|---|---|
| Bedrock | 8,000-25,000+ |
| Dense sand | 3,000-5,000 |
| Medium sand | 2,000-3,000 |
| Stiff clay | 2,000-4,000 |
| Loose sand | 1,500-3,000 |
| Soft clay | <1,500 |
Settlement
- Immediate (granular): rapid
- Consolidation (clays): slow, months to years
- Total vs differential: differential more damaging
- Typical max: 1" total, 1/2" differential for typical building
Frost depth (foundation minimum)
| Region | Depth |
|---|---|
| South Florida | 0" (no frost) |
| Mid-Atlantic | 24-30" |
| Midwest | 36-42" |
| N New England | 48-54" |
| N Minnesota | 60" |
Expansive vs collapsible soils
- Expansive (clay): swells with water, shrinks dry — foundations heave
- Mitigation: deep foundations bypassing zone, moisture control, structurally elevated slabs
- Collapsible (silt, loess): collapses when wetted — settlement
- Mitigation: pre-wetting/compaction, deep foundations
Lateral earth pressure
- At-rest, active, passive pressures
- Hydrostatic when below water table (drains critical)
- Surcharge from adjacent loads
- Designed by geotech + structural
- Drainage essential to prevent buildup
Waterproofing
- Membrane (sheet or fluid-applied)
- Drainage board (protects membrane)
- Perimeter drain (pipe in gravel to daylight or sump)
- Sump pump for low water level
- Vapor retarder on interior face
Foundation drainage
- Footing drains: perimeter pipe in gravel
- Slope to daylight or sump
- Filter fabric to prevent clogging
- Critical for basement spaces
12 Lateral Systems & Seismic Design
Lateral force-resisting systems
| System | R | Notes |
|---|---|---|
| Special steel moment frame | 8 | High ductility, large drift |
| Intermediate steel moment frame | 4.5 | Moderate seismic regions |
| Ordinary steel moment frame | 3.5 | Low seismic regions |
| Special steel braced frame | 6 | High strength, less drift |
| Special concrete moment frame | 8 | High ductility, ductile detailing |
| Special concrete shear wall | 6 | Stiff, common |
| Ordinary masonry shear wall | 2 | Lower performance |
| Light-frame wood shear wall | 6.5 | Residential |
Seismic base shear
V ≈ Cs × W
- W = effective seismic weight
- Cs = seismic response coefficient (per ASCE 7)
- Heavier buildings = more seismic force
- Lighter (steel, wood, mass timber) = less
Cs depends on
- Spectral acceleration (site location, mapped values)
- Site class (soil type — A rock to F poor)
- Period (T) of building
- R factor (system ductility)
- Importance factor (Ie — Risk Category)
Risk Category & Ie
| Category | Use | Ie |
|---|---|---|
| I | Low risk (sheds, ag) | 1.0 |
| II | Standard (most buildings) | 1.0 |
| III | High occupancy / substantial hazard | 1.25 |
| IV | Essential (hospitals, fire stations) | 1.5 |
Drift limits
- Typical 0.020 × story height (ordinary)
- 0.015 × h for hospitals, schools (Risk III/IV)
- 0.010 × h for some systems
- Story drift check separate from strength check
Diaphragms
- Rigid (concrete, well-attached steel deck): distributes load to walls by stiffness
- Flexible (untopped metal deck, wood): distributes by tributary area
- Semi-rigid: in between (most common, requires more analysis)
Soft story
A weak/soft level (often ground floor with parking or retail). Concentrates demand. Causes catastrophic collapse in earthquakes (Northridge 1994 examples). Need careful detailing or alternative configuration.
Wind vs seismic
Both lateral, but different characteristics:
- Wind: steady + gust, predictable distribution, high-rises governed
- Seismic: short-duration impulses, distributed per mass, low-rises often governed
- Building designed for worst case at each story
P-delta effects
Secondary moments from gravity loads acting on laterally deflected building. Becomes significant in tall buildings and ductile systems. Code triggers analysis at stability ratio thresholds.
Hurricane / high-wind areas
- HVHZ (High Velocity Hurricane Zone): Miami-Dade, Broward, parts of FL
- Special impact-resistant glazing or shutters
- Stricter component testing (ASTM E1996, E1886)
- Roof to wall to foundation continuous load path
13 Live Loads by Occupancy (IBC Table 1607.1)
Typical uniform live loads (psf)
Light loads (≤ 60 psf)
| Occupancy | psf |
|---|---|
| Residential — 1-2 family | 40 |
| Residential — apartments/dorms | 40-60 |
| Hospitals — patient rooms | 40 |
| Hotels — guest rooms | 40 |
| Schools — classrooms | 40 |
| Offices | 50 |
| Roofs (typical) | 20 |
Medium loads (60-100 psf)
| Occupancy | psf |
|---|---|
| Office corridors above first floor | 80 |
| Schools — corridors above first floor | 80 |
| Public corridors first floor | 100 |
| Stairs / exits | 100 |
| Assembly — fixed seating | 60 |
| Library — reading rooms | 60 |
| Stores — retail (1st floor) | 100 |
Heavy loads (100-150+ psf)
| Occupancy | psf |
|---|---|
| Assembly — movable seating | 100 |
| Lobbies | 100 |
| Sidewalks, vehicular driveways | 250 |
| Garages — passenger | 40 |
| Garages — trucks | varies |
| Library stacks | 150 |
| Manufacturing — light | 75 |
| Manufacturing — heavy | 125 |
| Storage — light | 125 |
| Storage — heavy | 250 |
Roof live loads
- Ordinary flat roof: 20 psf (reduces with tributary area)
- Snow load: per ASCE 7 ground snow map + modifiers
- Heavier roof live load required for green roofs (load varies)
14 Daylighting Design
Key metrics
DA (Daylight Autonomy)
- % of occupied hours daylight alone provides target illuminance (typically 300 lux)
- Target: DA300 ≥ 50% for primary occupied spaces
sDA (Spatial Daylight Autonomy)
- % of floor area meeting DA threshold
- LEED v4.1: sDA300/50% ≥ 55% for 1 point; ≥75% for 3 points
ASE (Annual Sunlight Exposure)
- % of area exposed to direct sun >1000 lux for >250 hours/yr
- Target: ASE1000,250 ≤ 10% to prevent glare/overheating
Daylight Factor (DF)
- Static metric: indoor/outdoor illuminance ratio
- DF >2% generally desirable
Strategies by orientation (N. Hemisphere)
North glazing
- Even, diffuse light
- No direct sun → no glare
- Best for art galleries, design studios
- Largest openings possible
South glazing
- Brightest in winter (low sun)
- Predictable shading with horizontal overhangs
- Best controlled in passive solar design
- Overhang depth: (winter solar altitude angle) determines
East/West glazing
- HARDEST to control
- Low sun angles → horizontal overhangs ineffective
- Need vertical fins or external shades
- Minimize glazing where possible (especially West)
Window-to-Wall Ratio (WWR)
- Energy codes typically limit WWR to 30-40%
- High WWR good for daylight but bad for heat loss/gain
- Trade-off: glazing performance vs. quantity
Light shelves
- Horizontal element above eye level
- Reflects daylight onto ceiling, deeper into space
- Effective for ~2× shelf height in penetration
- Combine with proper overhang
15 Parking Design Rules of Thumb
Stall dimensions (typical)
Standard
- 9' × 18' standard space
- 8' × 18' compact (where allowed by code)
- 10' × 20' large/luxury
Accessible
- 8' × 18' space + 5' access aisle = car-accessible
- 8' × 18' space + 8' access aisle = van-accessible
- OR 11' × 18' + 5' aisle for van
Aisle widths (between rows)
| Angle | One-way aisle | Two-way aisle |
|---|---|---|
| 90° | 24' (often) | 24' (often) |
| 75° | 18' | 26' |
| 60° | 16' | 24' |
| 45° | 13' | 22' |
Required spaces (ADA)
| Total spaces | Required accessible | Van-accessible |
|---|---|---|
| 1–25 | 1 | 1 |
| 26–50 | 2 | 1 |
| 51–75 | 3 | 1 |
| 76–100 | 4 | 1 |
| 101–150 | 5 | 1 |
| 151–200 | 6 | 1 |
| 201–300 | 7 | 2 |
| 301–400 | 8 | 2 |
| 401–500 | 9 | 2 |
| 501–1000 | 2% of total | 1 per 6 acc |
| Over 1000 | 20 + 1/100 | 1 per 6 acc |
Garage clearances
- Headroom: 7'-0\" min for standard; 8'-2\" for van-accessible
- Drive aisle clearance: 14' typical for trucks/emergency
- Sloped floor for drainage: ¼\"/ft minimum
- Ramp slope: 6% max for vehicular; transitions at top/bottom
Sizing calculations
- Surface lot: ~350-400 SF per car (incl aisle)
- Single-floor garage: ~325 SF per car
- Multi-level garage: ~300 SF per car (more efficient)
- Underground garage: ~350 SF per car
Code minimums (zoning typically)
- Office: 1 space per 200-400 SF
- Retail: 1 per 250-300 SF
- Restaurant: 1 per 100-150 SF (or per seat)
- Residential: 1-2 per unit
- Hotel: 1 per room + employees
16 Climate-Responsive Design
IECC Climate Zones (simplified)
Zone 1 — Very Hot (Miami, Honolulu)
- Cooling-dominated
- No heating typically required
- High humidity (Zone 1A)
- Strategies: shading, ventilation, reflective surfaces
Zone 2 — Hot (Houston, Phoenix)
- Cooling-dominated
- Hot humid (2A) or hot dry (2B)
- Strategies: shading, thermal mass (dry only), light colors
Zone 3 — Warm (Atlanta, LA, Dallas)
- Mixed cooling + some heating
- Most complex shading optimization
- Strategies: deep overhangs, cross-ventilation, modest insulation
Zone 4 — Mixed (Washington DC, Nashville)
- Significant heating AND cooling
- Hardest to optimize
- Strategies: balanced insulation, smart vapor management
Zone 5 — Cool (Chicago, Boston, Denver)
- Heating-dominated
- Strategies: high insulation, vapor retarder interior, solar gain in winter
Zone 6 — Cold (Minneapolis, Anchorage south)
- Strong heating dominance
- Strategies: very high insulation, triple-glazing, wind protection
Zone 7-8 — Very Cold / Subarctic
- Heating critical
- Strategies: super-insulation, minimal glazing, vestibules
Vapor retarder placement
- Zones 1-3: Exterior side (warm/humid outside)
- Zone 4: Vapor-open assemblies preferred; no vapor retarder
- Zones 5-8: Interior side (warm/humid inside)
Building orientation
- Long axis E-W generally optimal in most climates
- Maximizes north/south exposure (controllable)
- Minimizes east/west (uncontrollable)
Glass selection (SHGC, Solar Heat Gain Coefficient)
| Climate | Recommended SHGC |
|---|---|
| Hot (1-2) | 0.25 or lower |
| Mixed (3-4) | 0.25-0.40 |
| Cold (5-8) | 0.40-0.55 (capture winter sun) |
17 Structural Rules of Thumb
Beam depth (preliminary)
| Material | Depth ratio |
|---|---|
| Steel W-shape | Span / 20 |
| Steel joist | Span / 24 |
| Concrete beam | Span / 12-15 |
| Concrete one-way slab | Span / 24-28 |
| Concrete two-way slab | Span / 30-33 |
| Post-tensioned slab | Span / 35-45 |
| Wood joist | Span / 15-18 |
Typical span ranges
| System | Span (ft) |
|---|---|
| Wood joists | 12-22 |
| Light-gauge steel | 18-26 |
| Steel beam + deck | 30-50 |
| Steel girder + beam | 50-80 |
| OWSJ (K) | 30-60 |
| OWSJ (LH/DLH) | 60-240 |
| Concrete flat slab | 25-30 |
| Concrete waffle | 30-60 |
| Concrete PT | 30-40 |
Lateral systems
- Moment frame: Open plan, less efficient
- Braced frame: Efficient, blocks bays
- Shear wall: Very efficient, blocks entirely
- Dual system: Moment + braced/shear
Foundations
| Type | When |
|---|---|
| Spread footing | Good soil, columns |
| Strip footing | Bearing walls |
| Mat (raft) | Weak soil, full coverage |
| Driven pile | Deep bearing layer |
| Caisson | Heavy load, deep |
| Helical pier | Small load, low disturbance |
18 Envelope Systems
Four control layers (priority order)
- Water (bulk water) — sheds liquid
- Air — must be CONTINUOUS
- Vapor — warm side of insulation
- Thermal — continuous, avoid bridging
Rain screen principle
Cladding + air cavity + air/vapor barrier (inboard)
- Cladding sheds most water
- Cavity drains incidental water
- Air/vapor barrier handles the rest
- Decouples water from air/vapor management
Vapor retarder placement
| Climate | Side |
|---|---|
| Cold (zones 5-8) | Interior |
| Hot/humid (1A-2A) | Exterior |
| Mixed (zone 4) | Vapor-open or smart |
Curtain wall systems
| System | Use | Height |
|---|---|---|
| Storefront | 1-2 story | ≤20 ft |
| Window wall | Floor-supported | Mid-rise |
| Stick curtain wall | Slab-bypass, on-site | Mid-rise+ |
| Unitized curtain wall | Pre-fab panels | Mid-rise+ |
Thermal bridging mitigation
- Continuous exterior insulation (best)
- Thermal breaks at slab edges, balconies
- Steel stud cavities: continuous insul. on top
- Aluminum framing: thermally broken
19 MEP Sizing
Cooling loads (rule of thumb)
| Building type | Tons per SF |
|---|---|
| Office (efficient) | 1 / 400-500 |
| Office (older) | 1 / 250-350 |
| Retail | 1 / 200-300 |
| Restaurant | 1 / 100-200 |
| Lab/medical | 1 / 150-250 |
| Residential | 1 / 400-600 |
1 ton = 12,000 BTU/hr
Duct velocities (commercial)
| Run | Velocity (fpm) |
|---|---|
| Main supply | 1500-2500 |
| Branch supply | 700-1200 |
| Return | 500-1000 |
| Exhaust | 1500-2500 |
Sizing: A (sf) = Q (cfm) / V (fpm)
Electrical loads
| Building type | W/SF |
|---|---|
| Office | 6-8 |
| Retail | 8-10 |
| Restaurant | 15-25 |
| Lab | 25-50 |
| Data center | 100-300 |
Plumbing (Fixture Units)
| Fixture | DFU |
|---|---|
| Lavatory | 1 |
| WC (tank) | 3-4 |
| WC (flush valve) | 6-8 |
| Shower | 2 |
| Floor drain | 2 |
| Kitchen sink | 2 |
HVAC system types
- VAV — variable air volume, constant temp
- CAV — constant air, variable temp
- DOAS — dedicated outdoor air system
- Chilled beam — radiant cooling + DOAS
- VRF — variable refrigerant flow
20 Egress Detailed
Three components
- Exit Access — any point → exit
- Exit — protected (stair enclosure, passageway, exterior door at grade)
- Exit Discharge — exit → public way
Door swing
Swing in direction of egress when:
- Occupant load 50+
- Group H (any load)
- Horizontal exit
- Exit discharge (most cases)
Exit width sizing
Required width = Occupants × Factor
- Level egress (corridor, door): 0.2 in/occupant
- Stairs: 0.3 in/occupant
- Sprinklers reduce by ~80% (already in factors)
Minimum widths (most occupancies)
| Element | Min Width |
|---|---|
| Corridor | 44" |
| Door | 32" clear |
| Stairs | 44" |
| Aisle (Assembly w/ seats) | 36-66" |
Travel distance (sprinklered)
| Group | Max travel |
|---|---|
| A, E, F-1, M, R, S-1 | 250 ft |
| B, F-2, S-2, U | 300 ft |
| H-1 | 75 ft |
| H-2 | 100 ft |
| H-3 | 150 ft |
| H-4 | 175 ft |
| I-1, I-2, I-3 | 250 ft |
Common path of travel (sprinklered)
| Group | Max common path |
|---|---|
| Most (low occupant load) | 75-125 ft |
| H | 25-75 ft |
Dead-end corridor (sprinklered)
| Group | Max |
|---|---|
| B, F, S, U | 50 ft |
| Most others | 20 ft |
Two exits required when:
- Occupant load >49 (most)
- Common path exceeded
- Travel distance to single exit exceeded
- Some occupancies require sooner (H, I)
Three or more exits
- 3 exits: 501-1000 occupants
- 4 exits: >1000 occupants
21 Accessibility (ADA / ANSI A117.1)
Reach ranges
| Reach | Max | Min |
|---|---|---|
| Forward, unobstructed | 48" | 15" |
| Side, unobstructed | 48" | 15" |
| Forward, obstructed | 44" | — |
| Side, obstructed | 46" | — |
Maneuvering clearances
- Turning space: 60" circle OR T-shape
- Pull-side door: 60" deep × 18" beyond latch
- Push-side door: 48" deep × 12" beyond latch (if closer + latch)
- Knee clearance: 27" h, 30" w, 11" deep
- Toe clearance: 9" h, 6" deep
Routes & ramps
- Running slope <1:20 (5%) = accessible walking surface
- >1:20 = RAMP (max 1:12 / 8.33%)
- Max ramp rise: 30" per run
- Cross slope: 1:48 (2.08%) max anywhere
- Min width: 36" (48" preferred)
Stairs (accessible egress)
- Tread: 11" min
- Riser: 4" min, 7" max
- Uniform throughout flight
- Closed risers (no open backs)
- Handrails: 34-38" both sides
- Handrail extensions: 12" top, 1 tread depth bottom
Toilets
- Accessible stall: 60" w × 56" d (wall-hung)
- WC centerline: 16-18" from wall
- Seat height: 17-19"
- Grab bars: rear 36" min, side 42" min
- Flush controls: open side
- Door: out-swing or large stall
Parking
| Total spaces | Accessible | Van |
|---|---|---|
| 1-25 | 1 | 1 |
| 26-50 | 2 | 1 |
| 51-75 | 3 | 1 |
| 76-100 | 4 | 1 |
| 101-150 | 5 | 1 |
| 151-200 | 6 | 1 |
| 201-300 | 7 | 2 |
| 301-400 | 8 | 2 |
| 401-500 | 9 | 2 |
| 501-1000 | 2% of total | 1 per 6 accessible |
22 Structure
Lateral systems
- Moment frame — rigid joints; open plan; less efficient
- Braced frame — diagonals; efficient; obstructs openings
- Shear wall — solid wall; very efficient; blocks openings
- Dual system — moment + braced/shear
Loads
- Dead — permanent (structure, finishes, MEP)
- Live — variable (occupants, furniture)
- Wind — lateral pressure; location, height, exposure
- Seismic — ground acceleration; zone + site class
- Snow — ground snow load + roof factors
Typical bay sizes
- Wood: 16-20 ft
- Light steel: 18-22 ft
- Steel deck/concrete: 30-40 ft
- Concrete flat slab: 25-30 ft
- Long-span: 60-120 ft
23 Envelope
Four control layers
- Water (bulk water) barrier
- Air barrier — must be continuous
- Vapor retarder — warm side of insulation
- Thermal barrier — continuous to avoid bridging
Rain screen
Cladding + air cavity behind. Cladding sheds most water; air barrier (inside cavity) controls air/vapor. Decouples water management from air/vapor.
Thermal bridging
Conductive paths (steel studs, slab edges, balconies) bypass insulation — can drop effective R-value 40%+. Mitigate with continuous exterior insulation.
24 Egress
Three components
- Exit Access — any point to an exit
- Exit — protected (enclosed stair, exit passageway, exterior door)
- Exit Discharge — from exit to public way
Key distances (sprinklered)
- Common path — typ. 75–100 ft
- Dead-end corridor — typ. 20–50 ft
- Travel distance — typ. 200–300 ft
Egress width
Occupant load × factor:
- Level egress (corridors, doors): 0.2 in/occupant
- Stairs: 0.3 in/occupant
When 2 exits required
- Most occupancies: occupant load >49 OR common path exceeded
- 3 exits: 501-1000 occupants
- 4 exits: >1000 occupants
25 Accessibility
Slope thresholds
- <1:20 (5%): Accessible walking surface
- >1:20: Ramp territory
- Max 1:12 (8.33%) running slope for ramps
- Max 30\" rise per ramp run before landing
Clearances
- Turning radius: 60\" diameter circle
- Knee clearance: 27\" h × 11\" deep
- Toe clearance: 9\" h × 6\" deep
Accessible parking
- 1-25 spaces: 1 accessible
- 26-50: 2 / 51-75: 3 / 76-100: 4
- 1 of every 6 accessible must be van-accessible
Study PPD the way it's tested
Reading is the start. An account adds 140 spaced-repetition flashcards, 110 practice questions, and 3 timed mock exams for PPD — plus the other five divisions, synced across web, iOS, and Android.
Start your 7-day free trialThe other five divisions
Every plan includes all six. Study them in any order.